The PS series mechanical differential pressure switches offer a cost effective solution for filter, fan and duct pressure monitoring in building automation systems in the HVAC/R industry. PS series products offer field selectable switching point adjustment.
Technical data
- Accuracy of switching point (low limit typ.): ±8 Pa (PS1500: ±20 Pa, PS4500: ±100 Pa)
- Accuracy of switching point (high limit max.): ±15 %
- Service life: over 1 000 000 switching operations
- Electrical rating (resistive load): 3 A / 250 VAC (PS200: 0.1 A / 250 VAC)
- Electrical rating (inductive load): 2 A / 250 VAC (PS200: --)
- Operating temperature: -20...+60 °C
- Protection standard: IP54