wMBUS CMeX50 Concentrator
CMeX50 is a wireless M-Bus master which can be used by any existing wired M-Bus solution. Up to 500 slave wMBUS.
CMeX50 is a wireless M-Bus master which can be used by any existing wired M-Bus solution. The CMeX50 communicates with wireless M-Bus slaves via the wireless modes S1, S2, T1, T2, C1 and C2, and is compatible with all widely used M-Bus slaves on the market. The CMeX50 handles up to 500 wireless M-Bus slaves, which can be individually secured by encryption keys. It also has a built-in M-Bus master for 32 wired M-Bus slaves.
AUTOMATIC INSTALLATION
The CMeX50 can automatically install selected wireless M-Bus slaves. By enabling the CMeX50 Automatic installation mode, all wireless M-Bus slaves within range can be automatically detected and configured for operation. The installed wireless M-Bus slaves can later be edited and configured to use encryption for secure connections.
SIMPLE CONFIGURATION
The CMeX50 can easily be configured by using the intuitive display, or by using standard M-Bus commands on standard 2-wire M-Bus. The display shows current operation, installed wireless slaves, M-Bus operation modes and much more. There is no need for any extra tools to get the CMeX50 up and running.
USE IN EXISTING 2-WIRE M-BUS SYSTEM
All installed wireless M-Bus slaves can be readout using standard 2-wire M-Bus commands on the CMeX50 M-Bus slave port. This functionality makes the CMeX50 fully compatible with any existing wired M-Bus solution. The wireless M-Bus slaves can be individually readout using secondary or primary addressing mode with standard readout command REQ_UD2.
FUTURE PROOF
The CMeX50 can be remotely configured using standard M-Bus commands. When new M-Bus wireless modes or M-Bus standard updates are available, the firmware can be remotely updated to meet new market demands.
Features
Mechanics | Casing material | Polyamide |
Protection class | IP20 | |
Dimensions | 90 x 65 x 107 mm | |
Weight | 220 g | |
Mounting | DIN-enclosure | |
Connection M-Bus master | Screw terminal cable 0.5-2.5 mm², 0.5 Nm tightening torque | |
Connection M-Bus slave | Pin terminal solid wire 0.6-0.8 ø mm | |
Connection power supply | Screw terminal cable 0.5-2.5 mm², 0.5 Nm tightening torque | |
Connection antenna | SMA-f | |
Connection RS232 | RJ45 8/8 | |
Connection USB | Mini USB type B | |
Connection IR communication | CMe-, CMeX Series, ABB electricity | |
Electrical | Nominal Voltage | 100-240 VAC |
Voltage range | -10 % to +10 % of nominal voltage | |
Frequency | 50/60 Hz | |
Power consumption | 6 W | |
Installation category | CAT 2 (overvoltage category) | |
Environmental | Operating temperature range | -30 to +55 °C |
Storage temperature range | -40 to +85 °C | |
Operating humidity max | 80 % RH temperatures up to 31 °C, decreasing linearly to 50 % RH at 40 °C | |
Pollution | Degree 2 | |
Operating altitude | 0-2000 m | |
Usage | Indoor use only, can be extended with IP6X enclosure for outdoor use | |
User interface | LCD display | Graphic monochrome |
Display resolution | 128 x 64 dots | |
Keyboard | 7 illuminated buttons | |
Wired M-Bus master | M-Bus standard | EN 13757 |
Maximum connected M-Bus meters | 32 T | |
Maximum cable length | 1000 m | |
Break signal length M-Bus 2-wire and right IR interface | 45 ms | |
Nominal voltage | 28 VDC | |
Baud rate | 300, 2400 baud | |
Wireless M-Bus master | M-Bus standard | EN 13757-4 |
OMS-compliant | Yes | |
Wireless M-Bus modes | S1 S2 T1 T2 C1 C2 | |
Radio frequency band | 868 MHz | |
RF output power | 14 dBm | |
RF sensitivity | -105 dBm | |
Maximum slaves | 500 | |
Encryption | AES-128 | |
Wired M-Bus slave | M-Bus standard | EN 13757 |
M-Bus voltage | 21-42 VDC | |
Power consumption | 1.5 mA 1T | |
M-Bus baud rate | 300, 2400 Bit/s | |
M-Bus commands | SND_UD, SND_NKE, REQ_UD2 | |
M-Bus address default | 251 | |
Addressing modes | Secondary, primary | |
Approvals | Safety | EN 61010-1 |
Electromagnetic compatibility (EMC) | EN 61000-6-2 | |
Electromagnetic compatibility (EMC) | EN 61000-6-3 |