MODBUS RTU slave IO serial module with 16 digital inputs and 8 bistable relay outputs
RESI-16DI8RO-MODBUS:Serial IO module with RS485 with MODBUS/RTU slave protocol and 16 digital inputs (12..48Vdc) and 8 bistable relay outputs (max. 250Vac, 16A, 200µF)
MODBUS/RTU module to control socket-outlets, light applications and capacitive loads, with 8 bistable relays (max 250Vac, max. 16A, max. 200µF) and with 16 digital inputs for 12-48Vdc signals via serial bus, switchable loads: Incandescent lamp 4.800W, Fluorescent lamp not compensated 5.000W, Fluorescent lamp parallel compensated 2.500W/200µF, Fluorescent lamp duo-combination 2x5.000W, Halogen lamp (230VAC) 5.000W, Low voltage halogen lamp with transformer 2.000VA, Mercury arc sodium discharge lamp not compensated 5.000W, Mercury arc sodium discharge lamp parallel compensated 5.000W/200µF, Dulux lamp not compensated 4.000W, Dulux lamp parallel compensated 3.000W/200µF
Features
- Host communication: via RS485 with MODBUS/RTU slave protocol
- Host baud rates: 4800, 9600, 19200, 38400, 57600, 115200, 230400 or 256000
- no or even parity, 8 data bits, 1 stop bit
- configuration and testing of module with free PC software MODBUS configurator
- Weight: 560g, Dimension (LxWxH): 143x110x62mm
- Power supply: 12-48V=
- Power consumption: <0.5W
- Mountable onto a EN50022 DIN railor wall mounting.