Multi protocol operation
HART Master, Foundation fieldbus Host and PROFIBUS PA Master (available from Q3 2018) included in one device
Temporary attachment to fieldbus segments or HART loops for individual interaction with field devices
Fully compliant protocol implementations allow for interference-free access to running plants
Host communication via Bluetooth or USB
Built-in batteries and Bluetooth communication enable use of handheld host devices like smart phones and tablets
USB interface for bench host operation
Support of FDT Frame Applications and major Engineering Tools
PACTware FDT Frame Application and HART Communication DTM included
Communication DTM for Foundation fieldbus and PROFIBUS PA (optional)
Foundation fieldbus configuration tool (optional)
Application Program Interface for integration into Engineering Systems
Suitable for use in hazardous areas
EX approval for Zone 1
Suitable for connection to intrinsically safe circuits
Suited for harsh environment
Technical Specifications
- User Interface
- Controls: Power on/off button, Bluetooth pairing button
- Status LEDs: FIELDBUS (Fieldbus mode), HART (HART mode), Bluetooth (Pairing/Bluetooth active), Low battery, Power on
- Interfaces and Connectors
- USB:
- Speed: USB 2.0 Full Speed
- Connector: USB Type C
- Electrical: Non intrinsically safe. Do not use inside hazardous areas. 5V, 100mA. Um = 253V
- Bluetooth:
- BT mode: BT Classic, 2.4 - 2.478 GHz
- Output Power: +8 dBm (maximum)
- Fieldbus:
- Connection: 4 mm banana type jacks (red/black), polarity has to be observed
- Physical Layer: according to IEC 61158-2, Type 1: 31.25 Kbit/s, voltage mode
- Nominal input current (Fieldbus): 10 mA in Bluetooth and regular USB mode ; 18 mA (with Ufieldbus > 9,5V) for increased battery life time in USB mode (controlled by application)
- Terminatore Fieldbus: Nessun terminatore fieldbus incluso
- HART:
- Connection: 4 mm banana type jacks (red/black)
- Physical Layer: HART FSK compliant modem
- Operation in Hazardous Areas
- Intrinsic Safety Parameters
- EX ia IIB, Ui = 30 V or FISCO field device
- Isolation: 1500 VDC between USB and Fieldbus, 1500 VDC between USB and HART
- Physical Properties
- Power Supply:
- Battery: 3 * Alkaline, IEC-LR6, nominal voltage 1,5V
- For use in hazardous area: Energizer E91 or Duracell Procell MN1500.
- With batteries of other types or manufacturers certification is void.
- Fieldbus interface (Medium Attachment Unit) powered by fieldbus.
- Operating Temperature:
- Storage:
- Store batteries in a dry place at normal room temperature.
- Relative Humidity:
- Protection Class
- IP 54 (if USB port covered with cap)
- Dimensions (L x W x D): 175 mm x 74 mm x 32 mm
- Weight: 330 g (incl. batterie)