The QI-300-V-485 is a direct and alternating current transformer, galvanically isolated from the measuring circuit. The device is in function and appearance quite similar to a standard active CT, but capable of measuring the DC and AC component TRMS.
The transformer is equipped with an RS485 Modbus serial output and an analog 0-10V output. Through the serial port, it is possible to freely configure the span and zero and assign the Modbus address.
Features
- POWER SUPPLY: 12… 30Vdc, Reverse polarity and overtemperature protection
- CONSUMPTION: Maximum 20mA
- DEGREE OF PROTECTION: IP20
- PRECISION CLASS: 0.5% F.S.
- RESOLUTION: 12 bit
- TEMPERATURE COEFFICIENT: <200 ppm / ° C
- RESPONSE SPEED: 1000 ms
- WORKING TEMPERATURE: -15… + 65 ° C
- TYPE OF MEASUREMENT: RMS (monopolar) or DC
- CAPACITIES: 300 A AC / DC, custom scales settable via RS485
- CREST FACTOR: 1.4
- PASS BAND: DC or 20… 2000 Hz
- INSULATION: 3 kV on bare cable
- OVERLOAD: 2kA impulsive, 300A continuous
- OUTPUT: 0… 10V and RS485